By Sandun A Jayasekera
The Electrical Superintendent at the Kerawalapitya Grid sub-station as well as the Protection Scheme of the Ceylon Electricity Board (CEB) must take the responsibility for the island wide power outage on August 17, the interim report of the nine member committee that probed the biggest ever blackout in the country, has concluded.
The report strongly recommends a standard compliant, systemic, fool proof, safe procedures and maintenance protocols to be instated in CEB during operations and maintenance to prevent a repetition of a major breakdown of power supply of this magnitude in future.
Prof. Rahula Attalage, chairman of the committee told the media yesterday that the committee in its inquiry found that the key reason for the nationwide power interruption on the August 17, 2020 was due to the 3 Phase to Ground busbar fault that resulted in incorrect operation of the Busbar 2 Isolator of the Bus Coupler Bay by the Electrical Superintendent in Charge at the Kerawalapitiya Grid Substation.
“Kerawalapitiya Grid substation tripping was due to failure to follow the correct maintenance procedure by the relevant officials including the Electrical Superintendent. The committee also observed that there is no written maintenance protocol for this maintenance job inline with the current best practiced maintenance protocols,’ he said.
Add comment
Comments will be edited (grammar, spelling and slang) and authorized at the discretion of Daily Mirror online. The website also has the right not to publish selected comments.
Reply To:
Name - Reply Comment
On March 26, a couple arriving from Thailand was arrested with 88 live animal
According to villagers from Naula-Moragolla out of 105 families 80 can afford
Is the situation in Sri Lanka so grim that locals harbour hope that they coul
A recent post on social media revealed that three purple-faced langurs near t